R-134A Conversion Problem[240-260/85] posted by Andy Peck on
Sunday, 10 May 1998, at 7:09 a.m.
My daughter's 85 240 had no freon in it when I purchased it, so decided to convert to R-134a. Purchased a conversion kit (Interdynamics) at the local parts store which consisted of fittings and 2 cans of oil charge. System capacity is supposed to be 2.9 lbs of freon.
Started project yesterday. System accepted two cans of freon, but wouldn't accept oil charge. Calls for two 4 1/2 cans and I couldn't even get one in. Sight glass continues to have bubbles (sign of low charge).
What's the secret for getting the system to accept full charge? Should I get vacuum pump to pull system down? Any other suggestions??
Andy
Re: R-134A Conversion Problem[240-260/85] posted by Mikey on
Sunday, 10 May 1998, at 5:25 p.m.
R-134a conversion requires that you replace the reciever-dryer,o-rings,
expansion valve and fittings. Additionally,the condensor should be flushed
and the oil should be poured out of the compressor. A york compressor is
compatible with ester oil. A sanden compressor has a Viton seal on the front shaft which is not compatible with ester or PAG oils and must be changed.
Evacuate the system of R-12 then remove compressor and reciever-dryer.
Flush condensor. Replace all o-rings with R-134a compatible rings. Install
new expansion valve , reciever dryer and fittings.There should be a small amount
of oil added to the compressor and reciever- dryer prior to installation.
This oil should be ester oil. Ester oil mixes well with any residual mineral
oil left in the system. PAG oil comes in some retrofit kits, including Volvo's.
PAG oil does not mix well with residual mineral oil.The use of PAG oil will result in a degradation of cooling performance unless the ENTIRE system is flushed which requires flushing the evaporator and much time/money. So ester oil is a time saver.Once the system is reassembled, it must be vacuumed down to remove water vapor then R-134a should be added.The charge amount is about
80% of the r-12 charge. Put in one pound and check for leaks,the s-l-o-w-l-y-
add R-134a until the 80% (R-12) charge is in . It may be necessary to run the engine to get the entire charge in. Watch gauge pressures and vent temperatures
to get desired performance.A fan on the condensor is a must for good performance in hi-temp hi-humidity conditions.
More info on retrofit procedures can be found thru IMACA at 1-817-338-1100.
Remember that poor R-134a performance may be due to system component trouble,just as with R-12.
--
Mikey-1984 242 ti-ice cold R-134a air
Re: R-134A Conversion Problem[240-260/85] posted by chris on
Sunday, 10 May 1998, at 9:41 p.m.
There is a great bulletin board for air conditioning problems located at:
http://www.aircondition.com. They can probabbly help out with any A/C questions you might have.
The previous post should answer most of your questions, but it should be stressed that you MUST evacuate the system once it's been opened. It sounds like maybe you didn't do this. You just won't get the charge to "fit" in the system. Also, evacuating the system removes all the moisture from the system. If there is any moisture in the system, it will freeze in the expansion valve, causing a blockage, until it thaws, and then it will cool again until it refreezes.
For what it's worth, the opinions of most A/C techs I have spoken with is that your best bet is to stay with R-12 as long as it's available.
********** If anyone is looking to buy R-12 but doesen't have the EPA required license, follow the above link to find how to get it. You can take the test for it on the internet and receive your license in the mail. I did it and had no problems.